          Home > News&Events > Company news > How is the furnace pressure controlled in a regenerative aluminum melting furnace?
          Latest News
          Furnace pressure control in regenerative aluminum melting furnaces is a critical factor in ensuring melting efficiency, reducing energy consumption, and extending the service life of the furnace body...
          2026.04.20
          Exploring the Aluminum Processing Scenarios Suitable for Regenerative Aluminum Melting Furnaces..
          2026.04.19
          The core principle for regenerative aluminum melting furnaces is rapid assessment and decisive action, consistently prioritizing personnel safety above all else...
          2026.04.18
          Investigating the Core Impact of High Converter Processing Capacity on Copper Smelters..
          2026.04.18
          The core systems or components of a copper converter primarily comprise the following aspects:..
          2026.04.17

          How is the furnace pressure controlled in a regenerative aluminum melting furnace?

          Release time:2026-04-20 08:38 Views:

          Furnace pressure control in regenerative aluminum melting furnaces is a critical factor in ensuring melting efficiency, reducing energy consumption, and extending the service life of the furnace body. Its core logic lies in balancing the volume of gases within the furnace by regulating the rate of flue gas discharge.

          13.jpg

          1. Control Principles and Core Loops

          Furnace pressure control is deeply coupled with the flue gas control loop. The system employs a differential pressure transmitter to continuously monitor the pressure difference between the interior and exterior of the furnace chamber in real time, converting these pressure signals into 4–20 mA current signals for input into a PLC (Programmable Logic Controller). Within the PLC, a PID (Proportional-Integral-Derivative) closed-loop control module compares the actual measured pressure against a preset target value (typically a slight positive pressure, such as 10–30 Pa), subsequently issuing control commands to the actuator—usually an electric modulating butterfly valve located on the auxiliary flue.

          2. Key Execution Logic

          When furnace pressure rises (e.g., immediately after charging or during the instant of flow reversal): The PLC commands the valve to open wider, allowing a greater volume of high-temperature flue gas to be rapidly vented through the auxiliary flue—or discharged after passing through the regenerator—thereby reducing the volume of gas retained within the furnace.

          When furnace pressure drops or becomes negative: The valve opening is reduced, restricting flue gas discharge; this allows gases to accumulate within the furnace, causing the pressure to rise back to the target level.

          3. Specific Considerations for Regenerative Operation

          Since regenerative systems utilize a dual-regenerator configuration with alternating flow reversals (typically switching every 30–60 seconds), the resistance within the flue gas discharge channel fluctuates violently during the instant of reversal, leading to periodic, abrupt spikes in furnace pressure. Consequently, advanced control systems incorporate a "reversal synchronization feed-forward" mechanism: the valve opening is pre-adjusted slightly just prior to the reversal action to suppress these pressure spikes.

          4. Safety Protection and Optimization

          Furnace Door Interlock: The moment the furnace door is opened, the system automatically switches to a "pressure-priority" mode to force flue gas extraction, thereby preventing high-temperature gases from jetting out and causing injury to personnel.

          Overpressure Protection: If the furnace pressure exceeds a critical limit, the system triggers an emergency response—either by opening the explosion-relief door or by fully opening the flue damper.

          Through the coordinated operation of the aforementioned PID closed-loop regulation and reversal logic, furnace pressure fluctuations in regenerative aluminum melting furnaces can be maintained within a tight tolerance of ±5 Pa. This effectively prevents the ingress of cold air—which could lead to the oxidation of molten aluminum and hydrogen absorption—while simultaneously avoiding flame leakage from the furnace door that could damage the sealing structures.


          主站蜘蛛池模板: 国产精品久久久久亚洲| 亚洲精品在线观看毛片| 亚洲av首页在线| 亚洲激情国产一区二区三区| 97日日碰日日摸日日澡 | 国产精品人人爽人人爽av〖网:?1?7?6.?2?2〗| 精品日产一卡2卡三卡4卡自拍| 国产目拍亚洲精品二区| 亚洲网在线| 国产嫖妓一区二区三区无码| 国产清纯在线一区二区| 一群老熟女69| 亚洲成人黄色AV| 亚洲图片综合| 亚洲国产精品久久久天堂麻豆宅男 | 国产精品自拍卡一卡二| 国产精品美女久久久久浪潮AVⅤ| 中文字幕亚洲人妻一区| 成人三级片在线观看| 久久综合受美利坚合众国保护| 欧美午夜福利| 一区二区三区在线 | 欧洲| 亚洲av自拍| 国产精品视频色尤物yw| 91无码人妻精品一区二区蜜桃| 能把下面看湿的视频| 国精品人妻无码一区二区三区性色| 99精品久久久中文字幕| 欧美成人精品三级在线观看| 午夜熟妇乱子伦A视频| 热99精品只有里视频精品| 国产激情一区二区三区不卡| 国产蜜臀av在线一区尤物 | 欧美人与性囗牲恔配| 国产AV影片麻豆精品传媒| 国产精品手机在线观看你懂的| 一区二区亚洲人妻精品| 国产欧美日韩在线一区| 国产精品久久九九99九九99| 国产在线精品一区二区三区| 四虎在线成人免费观看|